Overview β
Reference configuration for Eastron SDM630-Modbus V2 (RS485) connected via Protoss PE11 RS485βEthernet gateway and consumed by Home Assistant Modbus TCP.
This document reflects a known-working setup.
1. Eastron SDM630 settings (meter) β
Configured directly on the SDM630 front panel.
Protocol: Modbus RTU
Baud rate:
9600Data bits:
8Stop bits:
1Parity:
NoneSlave address (Unit ID):
1RS485 wiring:
A / D+β PE11A / D+B / D-β PE11B / D-- Common GND recommended
Termination:
- Short cable: OFF
- Long cable: ON at one end only
If A/B are swapped, the meter will not respond at all.
2. Protoss PE11 β Serial (UART) configuration β
UART / Serial settings:
- Mode: RS485
- Baud rate:
9600 - Data bits:
8 - Stop bits:
1 - Parity:
NONE - Flow control:
Disabled
Protocol-related settings:
- Protocol: Modbus
- Frame Length:
16 - Frame Time:
100 ms - Gap Time:
50 ms - Buffer Size:
512
These timings are tolerant enough for SDM630 and prevent silent-frame issues.
3. Protoss PE11 β Network / Modbus bridge β
PE11 acts as a Modbus TCP server β Modbus RTU master.
Socket (NETP) configuration:
- Protocol:
TCP-SERVER - Local Port:
502 - Server Address:
0.0.0.0 - Route:
uart - Max connections:
3 - KeepAlive:
60
Important notes:
- No "transparent TCP" / virtual COM modes
- No Unit ID remapping
- No register base offset
- PE11 forwards Modbus TCP Unit ID directly to RTU slave
4. Health check (PE11 status page) β
When working correctly, you should see:
Serial Port State:
- Received Bytes: increasing
- Sent Bytes: increasing
- Received Frames > 0
- Failed Frames = 0
Communication State (netp):
- State:
Connected - Frames sent/received both increasing
- State:
If Serial Received Bytes = 0, the problem is wiring or serial config.
5. Home Assistant β Modbus TCP template β
Minimal working example:
modbus:
- name: eastron
type: tcp
host: 192.168.1.99
port: 502
timeout: 10
delay: 10
message_wait_milliseconds: 1000
sensors:
- name: "SDM630 Phase 1 Voltage"
slave: 1
address: 0 # 30001 β address 0
input_type: input
data_type: float32
precision: 2
unit_of_measurement: "V"
device_class: voltage
- name: "SDM630 Phase 2 Voltage"
slave: 1
address: 2 # 30003 β address 2
input_type: input
data_type: float32
precision: 2
unit_of_measurement: "V"
device_class: voltageNotes:
- Home Assistant uses 0-based addressing
- SDM630 input registers start at 30001
float32is big-endian, works correctly with SDM630
6. Common failure causes (quick checklist) β
- RS485 A/B swapped
- Wrong PE11 mode (transparent TCP instead of Modbus)
- Slave ID mismatch (not 1)
- Register base offset enabled in gateway
- Parity accidentally changed
7. Optional isolation test β
If things break again:
- Connect SDM630 directly via USBβRS485
- Test with
mbpoll/modpoll - If direct RTU works β PE11 config is the issue
End of reference