Overview ​

Reference configuration for Eastron SDM630-Modbus V2 (RS485) connected via Protoss PE11 RS485β†’Ethernet gateway and consumed by Home Assistant Modbus TCP.

This document reflects a known-working setup.

1. Eastron SDM630 settings (meter) ​

Configured directly on the SDM630 front panel.

  • Protocol: Modbus RTU

  • Baud rate: 9600

  • Data bits: 8

  • Stop bits: 1

  • Parity: None

  • Slave address (Unit ID): 1

  • RS485 wiring:

    • A / D+ β†’ PE11 A / D+
    • B / D- β†’ PE11 B / D-
    • Common GND recommended
  • Termination:

    • Short cable: OFF
    • Long cable: ON at one end only

If A/B are swapped, the meter will not respond at all.

2. Protoss PE11 – Serial (UART) configuration ​

UART / Serial settings:

  • Mode: RS485
  • Baud rate: 9600
  • Data bits: 8
  • Stop bits: 1
  • Parity: NONE
  • Flow control: Disabled

Protocol-related settings:

  • Protocol: Modbus
  • Frame Length: 16
  • Frame Time: 100 ms
  • Gap Time: 50 ms
  • Buffer Size: 512

These timings are tolerant enough for SDM630 and prevent silent-frame issues.

3. Protoss PE11 – Network / Modbus bridge ​

PE11 acts as a Modbus TCP server β†’ Modbus RTU master.

Socket (NETP) configuration:

  • Protocol: TCP-SERVER
  • Local Port: 502
  • Server Address: 0.0.0.0
  • Route: uart
  • Max connections: 3
  • KeepAlive: 60

Important notes:

  • No "transparent TCP" / virtual COM modes
  • No Unit ID remapping
  • No register base offset
  • PE11 forwards Modbus TCP Unit ID directly to RTU slave

4. Health check (PE11 status page) ​

When working correctly, you should see:

  • Serial Port State:

    • Received Bytes: increasing
    • Sent Bytes: increasing
    • Received Frames > 0
    • Failed Frames = 0
  • Communication State (netp):

    • State: Connected
    • Frames sent/received both increasing

If Serial Received Bytes = 0, the problem is wiring or serial config.

5. Home Assistant – Modbus TCP template ​

Minimal working example:

yaml
modbus:
  - name: eastron
    type: tcp
    host: 192.168.1.99
    port: 502
    timeout: 10
    delay: 10
    message_wait_milliseconds: 1000
    sensors:
      - name: "SDM630 Phase 1 Voltage"
        slave: 1
        address: 0          # 30001 β†’ address 0
        input_type: input
        data_type: float32
        precision: 2
        unit_of_measurement: "V"
        device_class: voltage

      - name: "SDM630 Phase 2 Voltage"
        slave: 1
        address: 2          # 30003 β†’ address 2
        input_type: input
        data_type: float32
        precision: 2
        unit_of_measurement: "V"
        device_class: voltage

Notes:

  • Home Assistant uses 0-based addressing
  • SDM630 input registers start at 30001
  • float32 is big-endian, works correctly with SDM630

6. Common failure causes (quick checklist) ​

  • RS485 A/B swapped
  • Wrong PE11 mode (transparent TCP instead of Modbus)
  • Slave ID mismatch (not 1)
  • Register base offset enabled in gateway
  • Parity accidentally changed

7. Optional isolation test ​

If things break again:

  • Connect SDM630 directly via USB–RS485
  • Test with mbpoll / modpoll
  • If direct RTU works β†’ PE11 config is the issue

End of reference